I have a transformer with a 120V primary and a center tapped secondary,
each side producing 51V. I can see 4 wires comming out of the
secondary A, B, C, D where B & C are tied together forming the center
tap. I want to get more current at 51V than each individual side can
provide. Is there anything wrong with breaking the connection between
B & C and connecting A&C together and B&D together to make the
transformer into esentially a 120V primary, 51V secondary? I know I
could just do it and see what happens, but this is a heavy duty
transformer and I don't want to mess it up. Any advice would be
greatly appreciated. Thanks

Back to top
John Popelish
Guest





Posted: Tue Nov 15, 2005 5:35 pm    Post subject: Re: Basic Transformer Question Reply with quote

jalbers@bsu.edu wrote:
Quote:
I have a transformer with a 120V primary and a center tapped secondary,
each side producing 51V. I can see 4 wires comming out of the
secondary A, B, C, D where B & C are tied together forming the center
tap. I want to get more current at 51V than each individual side can
provide. Is there anything wrong with breaking the connection between
B & C and connecting A&C together and B&D together to make the
transformer into esentially a 120V primary, 51V secondary? I know I
could just do it and see what happens, but this is a heavy duty
transformer and I don't want to mess it up. Any advice would be
greatly appreciated. Thanks

Conceptually, there is nothing wrong with paralleling two similar
windings to get a single output with a higher current capability.
But, if one winding has any difference in turns count than the other,
the slight difference in voltage will cause current to circulate
through the two windings, heating them up.

I would connect one pair of ends together and measure the voltage
between the remaining pair of ends, to make sure that this voltage is
essentially zero, before connecting those ends together.
Back to top
Pooh Bear
Guest





Posted: Wed Nov 16, 2005 7:58 am    Post subject: Re: Basic Transformer Question Reply with quote

"jalbers@bsu.edu" wrote:

Quote:
I have a transformer with a 120V primary and a center tapped secondary,
each side producing 51V. I can see 4 wires comming out of the
secondary A, B, C, D where B & C are tied together forming the center
tap. I want to get more current at 51V than each individual side can
provide. Is there anything wrong with breaking the connection between
B & C and connecting A&C together and B&D together to make the
transformer into esentially a 120V primary, 51V secondary? I know I
could just do it and see what happens, but this is a heavy duty
transformer and I don't want to mess it up. Any advice would be
greatly appreciated. Thanks

Yes, you can do that.

As John says though., you need to be sure that both windings are of exactly
equal voltage ( i.e. the same number of turns ).

Graham

Back to top
jalbers@bsu.edu
Guest





Posted: Wed Nov 16, 2005 5:35 pm    Post subject: Re: Basic Transformer Question Reply with quote

I tried it and it seems to be working ok. There is a small voltage
difference of around .020V or 20mv. It doesn't seem to be causing any
overheating or other problems.
Back to top
Pooh Bear
Guest





Posted: Thu Nov 17, 2005 1:35 am    Post subject: Re: Basic Transformer Question Reply with quote

"jalbers@bsu.edu" wrote:

Quote:
I tried it and it seems to be working ok. There is a small voltage
difference of around .020V or 20mv. It doesn't seem to be causing any
overheating or other problems.

That's fine. In practice the 2 windings won't be *exactly* the same
voltage down to the millivolt level.

Graham
Back to top
Jasen Betts
Guest





Posted: Thu Nov 17, 2005 2:48 pm    Post subject: Re: Basic Transformer Question Reply with quote

On 2005-11-15, jalbers@bsu.edu <jalbers@bsu.edu> wrote:
Quote:
I have a transformer with a 120V primary and a center tapped secondary,
each side producing 51V. I can see 4 wires comming out of the
secondary A, B, C, D where B & C are tied together forming the center
tap. I want to get more current at 51V than each individual side can
provide. Is there anything wrong with breaking the connection between
B & C and connecting A&C together and B&D together to make the
transformer into esentially a 120V primary, 51V secondary? I know I
could just do it and see what happens, but this is a heavy duty
transformer and I don't want to mess it up. Any advice would be
greatly appreciated. Thanks

the safe way:

disconnect B and C , measure the resistance between A and C (it should be
infinite), if it isn't stop. connect A and C power it up and measure the voltage
between B and D, it should be 0, if it is it's safe to connect them.

Bye.
Jasen
Back to top
jalbers@bsu.edu
Guest





Posted: Thu Nov 17, 2005 5:35 pm    Post subject: Re: Basic Transformer Question Reply with quote

I hooked up a 7 amp load to the transformer last night and it is not
even begining to show any signs of strain. I was using a DVOM with the
10 amp AC setting. The DVOM was rated to function to 10A but the test
leads that came with it were certainly not. Before I reallized what
was happing, one of the test leads burt up. I don't think it hurt the
DVOM though.
Back to top
 
Post new topic   Reply to topic    Electronics Forum Index -> Basics All times are GMT
Page 1 of 1

 
You cannot post new topics in this forum
You cannot reply to topics in this forum
You cannot edit your posts in this forum
You cannot delete your posts in this forum
You cannot vote in polls in this forum



Home & Living New Topics
Contact Us
Powered by phpBB