Noisy UPS
Electronics Forum Index Electronics
Circuits, theory, electrons and discussions.
 
 FAQFAQ   MemberlistMemberlist     RegisterRegister 
 ProfileProfile   Log in to check your private messagesLog in to check your private messages   Log inLog in 
 
Google
 
Web ElectronicsHelp.net
Noisy UPS

 
Post new topic   Reply to topic    Electronics Forum Index -> Equipment
Author Message
Guest






Posted: Thu Jul 21, 2005 12:35 am    Post subject: Noisy UPS Reply with quote

I've just acquired an older 1.4 kVa BEST Micro Ferrups UPS, the one
with the huge and heavy ferro-resonant transformer.

I changed the battery, plugged it in, and it works great. Runtime is
excellent for home use. Just one thing though: It hums and buzzes
like an old neon sign ballast. Almost unbearable. I may not be able
to use it for home because of the noise. It's quite a buzz.

Is there anything I can do to eliminate or minimize this noise?

Back to top
Dave M
Guest





Posted: Thu Jul 21, 2005 6:46 am    Post subject: Re: Noisy UPS Reply with quote

On 20 Jul 2005 17:11:17 -0700, giroup01@videotron.ca wrote:

Quote:
I've just acquired an older 1.4 kVa BEST Micro Ferrups UPS, the one
with the huge and heavy ferro-resonant transformer.

I changed the battery, plugged it in, and it works great. Runtime is
excellent for home use. Just one thing though: It hums and buzzes
like an old neon sign ballast. Almost unbearable. I may not be able
to use it for home because of the noise. It's quite a buzz.

Is there anything I can do to eliminate or minimize this noise?


Probably not... Ferror-resonant transformers are inherently noisy, especially
those of several years ago. You might try opening the unit so that you can get
to the big transformer. ( Remove battery connections first!!!) See if
tightening the assembly bolts in the transformer offers any relief. If that
doesn't fix it, there's probably one thing left to do... consider building a
small housing for it and mount it outside the house. Run a wire from house
wiring to the UPS, and another back into house to feed equipment.
==============

Dave M

Never take a laxative and a sleeping pill at the same time!!
Back to top
Keyser Soze
Guest





Posted: Thu Jul 21, 2005 8:35 am    Post subject: Re: Noisy UPS Reply with quote

"Dave M" <masondg4xx4@cxxomcast.net> wrote in message
news:p8vtd1d4291nj43ojpiagkitd221o4u9fl@4ax.com...
Quote:
On 20 Jul 2005 17:11:17 -0700, giroup01@videotron.ca wrote:

I've just acquired an older 1.4 kVa BEST Micro Ferrups UPS, the one
with the huge and heavy ferro-resonant transformer.

I changed the battery, plugged it in, and it works great. Runtime is
excellent for home use. Just one thing though: It hums and buzzes
like an old neon sign ballast. Almost unbearable. I may not be able
to use it for home because of the noise. It's quite a buzz.

Is there anything I can do to eliminate or minimize this noise?


Probably not... Ferror-resonant transformers are inherently noisy,
especially
those of several years ago. You might try opening the unit so that you
can get
to the big transformer. ( Remove battery connections first!!!) See if
tightening the assembly bolts in the transformer offers any relief. If
that
doesn't fix it, there's probably one thing left to do... consider
building a
small housing for it and mount it outside the house. Run a wire from
house
wiring to the UPS, and another back into house to feed equipment.
==============

Dave M


I'm assuming that when you say "...excellent for home use." that you
may not have a 1kw load on the UPS.

It's possible that the ferro-resonant transformer needs a minimum
load to go into regulation without all that buzzing and humming.

Try adding a 100 or 200 watt incandescent lamp on the output to see if that
helps.

If it does then wire a lamp to the ferro-resonant transformer output
before it goes to the UPS circuit. This will keep it happy when the
mains are up and will not be an additional load when the UPS kicks in.

Back to top
als
Guest





Posted: Tue Aug 02, 2005 4:35 pm    Post subject: Re: Noisy UPS Reply with quote

Check the cap to the transformer. Make sure that all bolts are VERY
tight. The only time you should hear anything is possibly when the
UPS inverter is running (i.e., no A.C. input), and then not much.
I have a dozen of these things (1's, 1.4's, 1.5's, and some 5 kva)
here, and they are all silent, except for the fan(s).
<als>


In article <1121904677.130547.55990@z14g2000cwz.googlegroups.com>, giroup01@videotron.ca says...
Quote:

I've just acquired an older 1.4 kVa BEST Micro Ferrups UPS, the one
with the huge and heavy ferro-resonant transformer.

I changed the battery, plugged it in, and it works great. Runtime is
excellent for home use. Just one thing though: It hums and buzzes
like an old neon sign ballast. Almost unbearable. I may not be able
to use it for home because of the noise. It's quite a buzz.

Is there anything I can do to eliminate or minimize this noise?


--
No fancy sig. Replies to: fsmyth-AT-consolidated-DOT-net.
see also: http://people.txucom.net/andysm/pages/1st_page.html
Back to top
 
Post new topic   Reply to topic    Electronics Forum Index -> Equipment All times are GMT
Page 1 of 1

 
You cannot post new topics in this forum
You cannot reply to topics in this forum
You cannot edit your posts in this forum
You cannot delete your posts in this forum
You cannot vote in polls in this forum